Rockwell-automation 1797-OE8H FLEX Ex HART Analog Modules User Manual Manual de usuario Pagina 161

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 196
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 160
Publication 1797-6.5.3 - March 2006
Additional HART Protocol Information C-13
63 Read analog output
information
0 Analog output number
code
0 Analog output number
code
1 Analog output alarm
select code
2 Analog output transfer
function code
3 Analog output range
units code
4…7 Analog output upper
range value
(F)
8…11 Analog output lower
range value
12…15 Analog output
additional damping
value (seconds)
64 Write analog output
additional damping
value
0 Analog output number
code
As in command
1…4 Analog output
additional damping
value (seconds)
(F)
65 Write analog output
range value
0 Analog output number
code
As in command
1 Analog output range
units code
2…5 Analog output upper
range value
(F)
6…9 Analog output lower
range value
66 Enter/edit fixed
analog output mode
0 Analog output number
code
As in command
1 Analog output units
code
2…5
Analog output level
(4)
(F)
67 Trim analog output
zero
0 Analog output number
code
As in command
1 Analog output units
code
2…5 Externally measured
analog output level
(F)
Table C.6 Common Practice Commands
Command Data in Command Data in Reply
# Function Byte Data
Type
(5)
Byte Data
Type
(5)
Vista de pagina 160