Publication 1797-6.5.3 - March 2006
B-22 FLEX Ex HART Module Commands
Command 154
Command 154 is the Rebuild Up to 8 Specified Loops command.
Table B.25 Command 154 Request and Response Data Bytes
Byte Description Value
Request Data Bytes
0 CH_NUM_0 Channel number 0 —
1 COUNT_0 Number of bytes before next item
… CH_NUM_i Channel number i
… COUNT_i Number of bytes before next item
Response Data Bytes
0 CH_NUM_0 Channel number 0 —
1 COUNT_0 Number of bytes before next item
2 ERROR_0 Error 0 0 = Channel
number invalid
64 = Invalid
channel number
… CH_NUM_i Channel number i —
… COUNT_i Number of bytes before next item
… ERROR_i Error i
…… …
Command-specific Response Codes
5 Error Too few data bytes received
16 Error Access restricted
17 Error Too many items requested
32 Error Busy
Comentarios a estos manuales