Rockwell Automation Publication 750COM-UM002B-EN-P - October 2012 33
Configuring the Option Module Chapter 3
Restoring Option Module
Parameters to Factory
Defaults
As an alternate reset method, you can restore the option module parameters by
using a MEMORY folder menu item instead of using Device Parameter 14 -
[Reset Module] described in Resetting the Option Module
on page 32. The
MEMORY folder method provides two ways to restore the option module
Device and Host parameters:
ALL—restores ALL option module Device and Host parameters to their
factory default values.
MOST—restores MOST option module Device and Host parameters—
except the following which are used for network setup:
Device Parameter 07 - [Net Addr Cfg]
Device Parameter 09 - [Net Rate Cfg]
Follow these steps to restore option module Device and Host parameters to their
factory default values.
1. Access the Status screen, which is displayed on HIM powerup.
2. Use the or key to scroll to the Port in which the option
module is installed.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select Set Defaults.
6. Press the (Enter) key to display the Set Defaults pop-up box.
IMPORTANT
When performing a Set Defaults, the drive may detect a conflict and then not
allow this function to occur. If this happens, first resolve the conflict and then
repeat a Set Defaults action. Common reasons for a conflict include the drive
running or a controller in Run mode.
After performing a Set Defaults, you must enter ‘1’ (Reset Module) or power
cycle the drive so that the new values take effect. Thereafter, this parameter
will be restored to a value of ‘0’ (Ready).
TIP
If your application allows, you can also reset the option module by cycling
power to the drive (resetting the drive) or by using the HIM’s Reset Device
function located in the drives DIAGNOSTIC folder.