92 Rockwell Automation Publication 750COM-UM002B-EN-P - October 2012
Appendix B Option Module Parameters
About Parameter Numbers
Each parameter set is independently and consecutively numbered.
How Parameters Are
Organized
The Device parameters and Host parameters are separately displayed in a
Numbered List view order.
Device Parameters
Configuration Tool Numbering Scheme
HIM
Connected Components Workbench software
DriveExplorer software
DriveExecutive software
The Device parameters and Host parameters begin with parameter
01. For example, Device Parameter 01 - [Port Number] and
Host Parameter 01 - [Net to Drv DL 01] are parameter 01 as
indicated by this manual.
Explicit Messaging See Chapter 6
, Using Explicit Messaging and Appendix C,
DeviceNet Objects for details.
Parameter
No. Name and Description Details
01 [Port Number]
Displays the drive port into which the option module is installed.
Typically, this will be Port 4, 5 or 6.
Minimum: 0
Maximum: 7
Type: Read Only
02 [DLs From Net Cfg]
Sets the number of contiguous controller-to-drive Datalinks
(additional parameters) that are included in the network I/O
connection. Logic Command and Reference are always included
in the I/O connection. This parameter controls how many of the
contiguous Host [DL From Net xx] parameters (16 maximum)
are active. For example, if this parameter value is set to ‘5’, then
Host Parameters 01 - [DL From Net 01] through 05 - [DL
From Net 05] will be updated.
Default: 0
Minimum: 0
Maximum: 16
Type: Read/Write
Reset Required: Yes
03 [DLs From Net Act]
Displays the value of Device Parameter 02 - [DLs From Net
Cfg] at the time the drive was reset. This is the number of actual
contiguous controller-to-drive Datalinks that the drive is
expecting.
Minimum: 0
Maximum: 16
Type: Read Only
04 [DLs To Net Cfg]
Sets the number of contiguous drive-to-controller Datalinks
(additional parameters) that are included in the network I/O
connection. Logic Status and Feedback are always included in the
I/O connection. This parameter controls how many of the
contiguous Host [DL To Net xx] parameters (16 maximum) are
active. For example, if this parameter value is set to ‘5’, then Host
Parameters 17 - [DL To Net 01] through 21 - [DL To Net 05]
will be updated.
Default: 0
Minimum: 0
Maximum: 16
Type: Read/Write
Reset Required: Yes
05 [DLs To Net Act]
Displays the value of Device Parameter 04 - [DLs To Net Cfg] at
the time the drive was reset. This is the number of actual
contiguous drive-to-controller Datalinks that the controller is
expecting.
Minimum: 0
Maximum: 16
Type: Read Only
06 [Net Addr Src]
Displays the source from which the option module’s node address
is taken. This will be either the Node Address switches (Figure 1
on page 18) or the value of Device Parameter 07- [Net Addr
Cfg].
Values: 0 = Switches
1 = Parameters
Type: Read Only