Rockwell Automation Publication 750COM-UM004B-EN-P - September 2012 21
Installing the Option Module Chapter 2
Table 1 - Node Address Switch Settings
Descriptions of node address values are as follows.
The switch settings can be verified by viewing Device Parameter 06 - [Net Addr
Act], a read-only parameter, with any of the following drive configuration tools:
• PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM
• Connected Components Workbench software, version 1.02 or later
• DriveExplorer software, version 6.01 or later
• DriveExecutive software, version 5.01 or later
Node
Address
Node Address Switch
Node
Address
Node Address Switch
7654321 7654321
00 0000000 14 0001110
01 0000001 15 0001111
02 0000010 16 0010000
03 0000011 17 0010001
04 0000100 18 0010010
05 0000101 19 0010011
06 0000110 20 0010100
07 0000111
…
08 0001000 120 1111000
09 0001001 121 1111001
10 0001010 122 1111010
11 0001011 123 1111011
12 0001100 124 1111100
13 0001101 125 1111101
Node Address Value Description
00 If the Node Address value is set to ‘00’, the option module uses Device
Parameter 05 - [Net Addr Cfg] to set the Node Address. See Setting the
Node Address on page 30.
01…125 Node address used by the option module.
126 The default address setting.