Rockwell-automation 20-750-PBUS Profibus DPV1 Option Module Manual de usuario Pagina 78

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 96
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 77
78 Rockwell Automation Publication 750COM-UM004B-EN-P - September 2012
Appendix B Option Module Parameters
Host Parameters
Parameter
No Name & Description Details
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
[DL From Net 01]
[DL From Net 02]
[DL From Net 03]
[DL From Net 04]
[DL From Net 05]
[DL From Net 06]
[DL From Net 07]
[DL From Net 08]
[DL From Net 09]
[DL From Net 10]
[DL From Net 11]
[DL From Net 12]
[DL From Net 13]
[DL From Net 14]
[DL From Net 15]
[DL From Net 16]
Sets the port number and parameter number to
which the selected Datalinks should connect. Each
selected port/parameter will be written with data
received from the network. These are parameters
written by the controller (outputs from the
controller).
If setting the value manually, the parameter value
= (10000 * port number) + (destination parameter
number). For example, suppose you want to use
Host Parameter 01 - [DL From Net 01] to write
to Parameter 01 of an optional encoder module
plugged into drive Port 5. The value for Host
Parameter 01 - [DL From Net 01] would be
50001 [(10000 * 5) +1].
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Minimum: 0
Maximum: 159999
Type: Read/Write
Reset Required: No
Vista de pagina 77
1 2 ... 73 74 75 76 77 78 79 80 81 82 83 ... 95 96

Comentarios a estos manuales

Sin comentarios