Appendix B
Adapter Parameters
Appendix B provides information about the ControlNet adapter
parameters.
The parameters in the adapter are numbered consecutively. However,
depending on which configuration tool you use, they may have different
numbers.
Topic Page
About Parameter Numbers
B-1
Parameter List B-1
About Parameter Numbers
Configuration Tool Numbering Scheme
• DriveExplorer
• DriveExecutive
• HIM
The adapter parameters begin with parameter 1. For
example, Parameter 01 - [Mode] is parameter 1 as
indicated by this manual.
• Explicit Messaging
• RSNetWorx for ControlNet
Refer to Chapter 6
, Using Explicit Messaging, and
Appendix C, ControlNet Objects for details.
Parameter List
Parameter
No. Name and Description Details
01 [Mode]
Displays the Single or Multi-Drive operating mode
selected with the Operating Mode Jumper (J7) on
the adapter.
Default: 0 = Single Drv
Values: 0 = Single Drv
1 = Multiple Drv
Type: Read Only
02 [CN Addr Cfg]
Sets the ControlNet node address if the Node
Address Switches are set to “00.” (Updates
Parameter 03 - [CN Addr Act] after a reset.)
Default: 2
Minimum: 1
Maximum: 99
Type: Read/Write
Reset Required: Yes
03 [CN Addr Act]
Displays the ControlNet node address actually
used by the adapter.
Default: 2
Minimum: 1
Maximum: 99
Type: Read Only