Using Multi-Drive Mode 7-15
Figure 7.11 ControlLogix Drive 1 Control Subroutine (Continued)
13 Copy File
Source Drive_1_Speed_Reference
Dest Drive_Output_Image[3]
Length 1
COP
Explicit Messaging Example
Drive 1 parameters are accessed by adding 18432 decimal (4800 hex) to the desired parameter number. This example
reads data from Parameter d003 - [Output Current] by using an Instance of 18435 (18432 + 3).
14
Drive_1_Perform_Parameter_Read
EN
DN
ER
Type - CIP Generic
Message Control Drive_1_Parameter_Read_Message
...
MSG
Explicit Messaging Example
Drive 1 parameters are accessed by adding 18432 decimal (4800 hex) to the desired parameter number. This example
reads data from Parameter d003 - [Output Current] by using an Instance of 18435 (18432 + 3).
Drive 1 parameters are accessed by adding 18432 decimal (4800 hex) to the desired parameter number. This example
writes data to Parameter P039 - [Accel Time 1] by using an Instance of 18471 (18432 + 39).
15
Drive_1_Perform_Parameter_Write
EN
DN
ER
Type - CIP Generic
Message Control Drive_1_Parameter_Write_Message
...
MSG
Drive 1 parameters are accessed by adding 18432 decimal (4800 hex) to the desired parameter number. This example
writes data to Parameter P039 - [Accel Time 1] by using an Instance of 18471 (18432 + 39).
16
Return
RET
(End)