Using Multi-Drive Mode 7-19
Figure 7.13 ControlLogix Drive 3 Control Subroutine (Continued)
13 Copy File
Source Drive_3_Speed_Reference
Dest Drive_Output_Image[7]
Length 1
COP
Explicit Messaging Example
Drive 3 parameters are accessed by adding 20480 decimal (5000 hex) to the desired parameter number. This example
reads data from Parameter d003 - [Output Current] by using an Instance of 20483 (20480 + 3).
14
Drive_3_Perform_Parameter_Read
EN
DN
ER
Type - CIP Generic
Message Control Drive_3_Parameter_Read_Message
...
MSG
Explicit Messaging Example
Drive 3 parameters are accessed by adding 20480 decimal (5000 hex) to the desired parameter number. This example
reads data from Parameter d003 - [Output Current] by using an Instance of 20483 (20480 + 3).
Drive 3 parameters are accessed by adding 20480 decimal (5000 hex) to the desired parameter number. This example
writes data to Parameter P039 - [Accel Time 1] by using an Instance of 20519 (20480 + 39).
15
Drive_3_Perform_Parameter_Write
EN
DN
ER
Type - CIP Generic
Message Control Drive_3_Parameter_Write_Message
...
MSG
Drive 3 parameters are accessed by adding 20480 decimal (5000 hex) to the desired parameter number. This example
writes data to Parameter P039 - [Accel Time 1] by using an Instance of 20519 (20480 + 39).
16
Return
RET
(End)