Rockwell Automation Publication 520COM-UM004A-EN-E - November 2013 15
Installing the Adapter Chapter 2
Node Address Switch Settings
Description of Node Address Switches
The switch settings can be verified by viewing the Device parameter 06 [Net
Addr Act], a read-only parameter, with any of the following drive configuration
tools:
• PowerFlex 520-series drive built-in keypad
• PowerFlex 22-HIM-A3 or 22-HIM-C2S HIM
• Connected Components Workbench software (version 3 or greater)
Connecting the Adapter to
the Drive
1. Remove power from the drive.
2. Use static control precautions.
3. Separate the drive’s control module from the power module.
Node
Address
Node Address Switch Node
Address
Node Address Switch
7654321 7654321
00 0000000 15 0001111
01 0000001 16 0010000
02 0000010 17 0010001
03 0000011 18 0010010
04 0000100 19 1010011
05 0000101 20 0010100
06 0000110
...
07 0000111 120 1111000
08 0001000 121 1111001
09 0001001 123 1111010
10 0001010 124 1111011
11 0001011 125 1111100
12 0001100 126 1111101
13 0001101 127 1111111
14 0001110
Node Address Value Description
00 or 127 If the Node Address switches are set to ‘00’ (the default setting) or 127, the adapter uses Device
parameter 05 [Net Addr Cfg] to set the Node Address. See Setting the Node Address
on
page 25.
01...126 Node Address used by the adapter.
ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain
high voltages that can cause injury or death. Remove power from the drive, and
then verify power has been discharged before connecting the adapter to the
network.