Rockwell Automation Publication 520COM-UM004A-EN-E - November 2013 19
Installing the Adapter Chapter 2
PROFIBUS Connector
4. Connect the PROFIBUS cable to the adapter and secure it with the two
screws on the connector.
Network Wiring Diagram
5. Ground the shield to reduce electrostatic pickup. However, shielding is
only effective when the shield is properly connected to ground. See the
PROFIBUS Installation Guideline for instructions to correctly ground the
shield.
IMPORTANT
PROFIBUS communication may not operate correctly if the cable shield
does not make full contact with the connector housing.
Terminal Signal Function
Housing Shield Bus cable shield (outer screen that surrounds A and B conductors)
1 Not connected
2 Not connected
3 B-LINE Positive RxD/TxD according to RS485 specification
4 RTS Request to send
5 GND BUS Network Zero Volt Reference (isolated from drive side)
6 +5V BUS +5V output to network (isolated from drive side)
7 Not connected
8 A-LINE Negative RxD/TxD according to RS485 specification
9 Not connected
B
A
B
A
B
A
B
A
A
B
AB