Rockwell Automation Publication 520COM-UM004A-EN-E - November 2013 53
Using Acyclic Messaging Chapter 6
Class 1 Acyclic Write for Host Parameter 41 [Accel Time 1]
To manually trigger the message to be sent, enter a value of ‘1’ into the
MVI69PDPMV1.MailboxCommand.Class1AcyclicWrite tag.
The message response status indicates success when the data in the
MVI69PDPMV1.Mailbox.Class1AcyclicWrite.In.ErrorDecode tag is a value of
‘0x00’. Note that any non-zero value indicates an error has occurred.
Class 1 Acyclic Write response data can be viewed as shown in Class 1 Acyclic
Write Response Data for Host Parameter 41 [Accel Time 1] on page 54.
Change value of tag to 1” to send
Class 1 Acyclic Write Command.
Copy or insert values for
parameter write request:
- Parameter Slot Number
- Slave Node Address
- Length of Data (Bytes)
- Parameter Index
- Data bytes...
(Data bytes may be copied from
a Local PLC Tag” with appropriate
data type specication)