Rockwell Automation Publication 520COM-UM004A-EN-E - November 2013 21
Installing the Adapter Chapter 2
Drive and Adapter Status Indicators
Configuring/Verifying Key Drive Parameters
The PowerFlex 520-series drive can be separately configured for the control and
Reference functions in various combinations. For example, you could set the
drive to have its control come from a peripheral or terminal block with the
Reference coming from the network. Or you could set the drive to have its
control come from the network with the Reference coming from another
peripheral or terminal block. Or you could set the drive to have both its control
and Reference come from the network.
Configuring the Host parameters can be done using the drive’s keypad, a HIM,
Logix Designer or Connected Components Workbench. In the following
example, the drive will receive the Logic Command and Reference from the
network.
1. Set the value of Host parameter P046 [Start Source 1]
to 4 “Network Opt”.
2. Set the value of Host parameter P047 [Speed Reference1]
to 4 “Network Opt”.
F
W
D
ENET LINK
EtherNet/IP
Item Status Indicator Status
(1)
(1) If all status indicators are off, the adapter is not receiving power. If any other conditions occur, see Troubleshooting on page 69.
Description
➊ PORT Green Normal operation. The adapter is properly
connected and is communicating with the
drive.
Flashing green The adapter is in the process of establishing a
connection to the drive. This status indicator
will turn solid green or red.
➋ MOD Green Normal operation. The adapter is operational
and is transferring I/O data.
Flashing green Normal operation. The adapter is operational
but is not transferring I/O data.
➌ NET A Green Normal operation. The adapter is properly
connected and communicating on the
network.
Flashing green The adapter is properly connected but is not
communicating with any devices on the
network.
➍ NET B Off Not used for PROFIBUS network.
➊
➋
25-COMM-P PowerFlex 525 Frame A shown
➌
➍
➊
➋
➌
➍