Chapter 4
Programming the RediPANEL Modules
4–10
After entering the ladder logic, place the PLC in the RUN or REMOTE RUN
mode to test your logic. Monitor the ON/OFF status of the input and output
bits of the RediPANEL push button module by pressing [SEARCH] 53
followed by the address to monitor. This displays the input or output image
table for that address.
The following figure shows what the I/O image table looks like when you
press push button #1 for the previous example.
120
03
00
Push Button #1, Illuminate the Lamp in Button #4
Input Image Table
1/4 Rack
Module Group
(Word)
00000 00001 00000 0 0001
1
0
Switch Status Bits
Lamp Control Bits
012345671011121314151617 012345671011121314151617
Output Image Table
1/4 Rack
Special Considerations
If the MODE SELECT DIP Switch #5 (Fault Table) on the 1772-SD2 is set
to OFF, a remote I/O fault table is generated and remote I/O rack #2 must be
declared used. These fault status bits are generated in the addresses
associated with Module Groups 5 and 6 of remote I/O rack #2. (See
Publication 1772-2.18).