Configuring the UDC Module’s Registers
3-41
Power Device Status Register (Continued) 204/1204
Inverter Power Device Fault Bit 6
The Inverter Power Device Fault bit is set if
the gate driver turns off an output power
device (IGBT) to protect it from an
overcurrent.
Bit 3 in register 202 will also be set.
Hex Value: 0040H
Sug. Var. Name: IPMA@
Access: Read only
UDC Error Code: N/A
LED: N/A
If an output short circuit occurs, a high current will flow in the IGBT causing its
collector-to-emitter voltage to increase to a level much higher than normal. The
gate driver detects this condition and instantly shuts off the IGBT to prevent its
destruction.
Bit 7
Reserved for future use.
Hex Value: 0080H
Sug. Var. Name:
Access: Read only
UDC Error Code: N/A
LED: N/A
Bit 8
Reserved for future use.
Hex Value: 0100H
Sug. Var. Name:
Access: Read only
UDC Error Code: N/A
LED: N/A
Bit 12
Reserved for future use.
Hex Value: 1000H
Sug. Var. Name:
Access: Read only
UDC Error Code: N/A
LED: N/A
Bit 13
Reserved for future use.
.
Hex Value: 2000H
Sug. Var. Name:
Access: Read only
UDC Error Code: N/A
LED: N/A