Configuring the UDC Module’s Registers
3-57
Meter Port 1
UDC Module Meter Port 1 Register Number Register 1002
UDC register number (0 - 2044) to be mapped to meter port 1. Sug. Var. Name: N/A
Units: N/A
Range: N/A
Access: Read/Write
UDC Module Meter Port 1 Bit Number Register 1003
Bit number of the UDC register specified in register 1002 that is to be
mapped to port 1. Enter a value of 100 (bit 00) to 115 (bit 15) as
required. Enter a value of zero if all of the registers bits are to be
displayed.
Sug. Var. Name: N/A
Units: N/A
Range: N/A
Access: Read/Write
UDC Module Meter Port 1 Maximum Value Register 1004
Set this register to the number that will represent +10V. The
maximum allowable value is 32767.
Sug. Var. Name: N/A
Units: N/A
Range: N/A
Access: Read/Write
UDC Module Meter Port 1 Minimum Value Register 1005
Set this register equal to the number that will represent -10V. The
minimum allowable value is -32768.
Sug. Var. Name: N/A
Units: N/A
Range: N/A
Access: Read/Write