3-6 Segregating Sources and Victims
Wire and Cable Categories
The table below indicates the best zone for running cables and wires.
The table also shows how the use of ferrite sleeves and shielded cable
can reduce the noise effects of dirty and very-dirty wires and cables.
Note: Some items have two entries (one shielded and one not
shielded).
Cable and Wire Category
Zone Method
Very-
Dirty
Dirty Clean Ferrite
Sleeve
1
Shielded
Cable
2
Three Phase between Line Filter and
Drive
X
Three Phase between Line Filter and
Drive
XX
Extended DC bus X
Extended DC bus X X
PWM Drive/Inverter to Motor Power
3
X
PWM Drive/Inverter to Motor Power X X
PWM Drive/Inverter to Sine Wave
Filter
X
Sine Wave Filter to Motor X
CM Choke to Motor Power X
CM Choke to Motor Power X X
Line Terminator - Motor Power X
Line Terminator - Motor Power X X
External Dump Shunt Resistor X
External Dump Shunt Resistor X X
Contactor to AC Motor X
Contactor to AC Motor X X
Three Phase Supply Power X
Single Phase Supply Power X
24V Hydraulic/Pneumatic - solenoids X
Motor Feedback Resolver X X
PLC digital I/O X
Dedicated Drive Inputs (except
registration)
X
Limit Switches X
Push buttons X