Publication GMC-RM001A-EN-P July 2001
10-2 Encoders
Wiring
Always use shielded cable (manufacturers usually specify
appropriate cable).
Segregate the cable as far as practical from dirty and especially
very-dirty wiring.
Power
Always use the internal power supply when available.
Ensure the power supply has a clean rating (refer to Figure 10.1
and Figure 10.2 for linear and switch-mode power supply
examples).
Use a filter if a switch-mode supply is used (refer to the chapter
Filtering Noise for more information).
Always ground the common.
Mounting
Insulate the encoder body from the machine structure and connect
it to the cable shield.
Note: This strategy also requires an insulated shaft coupling.
If the encoder cannot be insulated, connect the cable shield to
ground at the encoder case and drive chassis (or dedicated
termination).