Publication GMC-RM001A-EN-P July 2001
Chapter
7
Power Distribution
Chapter Objectives
This chapter describes bonding, segregating, shielding, and filtering
techniques when routing AC and DC power. This chapter covers the
following topics:
Understanding noise in power wiring
Three-phase power supplies
Single-phase power supplies
24V dc power supplies
Understanding Noise in
Power Wiring
AC and DC power wiring usually extends to all parts of a system.
Without precautions, noise coupled into any power wiring conductor
is distributed throughout the entire system.
Three-Phase Power
Supplies
To avoid noise related problems caused by three-phase power
supplies, observe the following guidelines.
Treat three-phase wiring as dirty.
Include line filters for loads that create noise, such as PWM
devices.
Line Filters
Observe the following guidelines when installing line filters.
Install an individual filter as close as possible to each PWM load
(this is the preferred configuration).
Install the filter and PWM device on the same panel.
Treat wiring between filter and drive as very-dirty (provide
shielding as required).
Segregate input and output wiring as far as possible.