Issue 13 May 13 PD-T8160 28
CONFIGURATION
PHYSICAL MODULE:
RACK 1: 16 BOOLEAN inputs. Voted states of the two 7411F boards as identified by the OEM
parameters.
RACK 2: 3 ANALOGUE inputs Channel 1 – Error status. i.e. 1 bit per pair of channels. LSB = first
channel. This is set when the corresponding channels of the
two boards disagree after the number of milliseconds
configured in the OEM parameter MSEC.
Channel 2 – Channel Faults (1 bit per channel) for the first module of the
pair. 1 – channel ok, 0 - channel fault
Channel 3 – Channel Faults (1 bit per channel) for the second module of
the pair. 1 - channel ok, 0 - channel fault
RACK 3: 2 BOOLEAN inputs Inputs reflecting the board status of the two 7411F boards specified.
Channel 1 is module 1 and Channel 2 is module 2. FALSE - board ok,
TRUE - board fault
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.
EXTRA INFORMATION
Error status:
The error status bits are only set IF channels disagree AND each channel is NOT in a
channel fault condition after MSEC has been exceeded.
The algorithm for the calculation of the error bits is:
Channel state Channel state Channel Fault Channel Fault Voted input Error bit
Board 1 Board 2 Board 1 Board 2 After MSEC Exceeded
Low Low In range In range Low 0
Low Low In range Fault Low 0
Low Low Fault In range Low 0
Low Low Fault Fault Low 0
Low High In range In range High 1
Low High In range Fault Low 0
Low High Fault In range High 0
Low High Fault Fault High 1
High Low In range In range High 1
High Low In range Fault High 0
High Low Fault In range Low 0
High Low Fault Fault High 1
High High In range In range High 0
High High In range Fault High 0
High High Fault In range High 0
High High Fault Fault Low 0
Entering the Threshold data:
At present the threshold values have to be entered as a count between 0 and 255, (8bit word), e.g. on
a -5V dc to 32V dc system:
COUNTS = (( VOLTAGE + 5 ) / 37) * 255
16V would be represented by:
(16+5)/37 = 0.567.
0.567 * 255 = 145 counts
0VDC would be represented by:
(0+5)/37 = 0.135
0.135 * 255 = 34 counts