Rockwell-automation T8160 Trusted TMR Interface Manual de usuario Pagina 44

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 80
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 43
Trusted
TM
TMR Module T8160
Issue 13 May 13 PD-T8160 44
4.22. I/O Complex Equipment ‘SX7441A’
Description: T7441A Digital Output Module, 24V dc. The Digital Output Module provides digitally
switched outputs for controlling 16 field loads. The 24V dc digital output circuits are
‘sourcing’ outputs that switch field power ranging from 18V dc to 32V dc. Field power
for the outputs is arranged in two isolated groups of 8 points. This board definition is
used in a simplex configuration.
Product Description reference: PD-T7015 DC Digital Output Module
OEM PARAMETERS:
OEM parameter Valid numbers Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where the
Module is placed.
CONFIGURATION
PHYSICAL MODULE:
RACK 1: 16 BOOLEAN outputs States to be written to the two modules identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
TRUE - channel high, FALSE – channel low
RACK 2: 1 BOOLEAN input Input reflecting the board status of the two modules specified. FALSE -
board ok, TRUE – board fault
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.
Vista de pagina 43
1 2 ... 39 40 41 42 43 44 45 46 47 48 49 ... 79 80

Comentarios a estos manuales

Sin comentarios