Trusted
TM
TMR Module T8160
Issue 13 May 13 PD-T8160 30
CONFIGURATION
PHYSICAL MODULE
RACK 1: 16 BOOLEAN inputs Input states of the module as identified by the OEM parameters.
RACK 2: 1 ANALOGUE input Channel Faults (1 bit per channel) for the module.
1 - channel ok, 0 – channel fault
RACK 3: 1 BOOLEAN input Input reflecting the board status of the module specified.
FALSE - board ok, TRUE – board fault
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.
EXTRA INFORMATION
Entering the Threshold data:
At present the threshold values have to be entered as a count between 0 and 255, (8bit word), e.g. on
a -5VDC to 32 VDC system:
COUNTS = (( VOLTAGE + 5 ) / 37) * 255
16 V would be represented by:
(16+5)/37 = 0.567.
0.567 * 255 = 145 counts
0VDC would be represented by:
(0+5)/37 = 0.135
0.135 * 255 = 34 counts