106Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
106 Configuring the Configurable Flowmeter Module
O.Total[0].Overspeed Decimal BOOL Enables the Overspeed alarm on output
connected to channel 0. When the Speed
exceeds the Highest Allowed Frequency
value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
1
O.Total[0].Acceleration Decimal BOOL Enables the Acceleration alarm on output
connected to channel 0. When the absolute
acceleration exceeds the Acceleration
Alarm value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
1
I.Status[0].ProverState Decimal SINT Displays status of the prover operation on
channel 0
0 = Prover Not Active
1 = Prover waiting for 1
st
start
2 = Prover waiting for 1
st
stop
3 = Prover waiting for 2
nd
start
4 = Prover waiting for 2
nd
stop
5 = Prover Complete
I.Status[0].TotalCounts Decimal DINT Displays actual pulses counted by the
counter connected to the channel 0
I.Status[0].FreqAverage Float REAL Displays frequency averaged over the Meter
samples on channel 0
I.Status[0].FreqPeriod Float REAL Displays frequency using sample time on
channel 0
I.Status[0].Speed Float REAL Displays frequency using filter resolution on
channel 0
I.Status[0].Acceleration Float REAL Displays acceleration on channel 0 as
calculated by using AccelCalculation
samples
I.Status[0].GrossVolume Float REAL Total Counts during each
Sample/K-factor x Meter Factor as occurs on
channel 0
I.Status[0].NetVolume Float REAL Total Counts during each
Sample/K-factor x MeterFactor x CCF) as
occurs on channel 0
I.Status[0].GrossRate Float REAL Total Counts in Meter Sample/ (K-factor x
Sample Interval) x Meter Factor as occurs on
channel 0
I.Status[0].NetRate Float REAL Total Counts in Meter Sample/ (K-factor x
Sample Interval) x Meter Factor x CCF as
occurs on channel 0
Table 8 - Tag Changes Required for Totalizer Mode Using Prover Function
Name Style Data type Definition Enter this
Value