134Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
134 Software Configuration Tags
O.Total[1].Control Binary SINT
O.Total[1].Reset Decimal BOOL
O.Total[1].Load Decimal BOOL
O.Total[1].ProverEnable Decimal BOOL Enables the prover operation on output connected to
channel 1. Once this bit is enabled, the module waits
for output Z
0
to energize before beginning prover
operations.
0 = Prover operation is disabled
1 = Prover operation is enabled
O.Total[1].FillEnable Decimal BOOL Enables the filling operation on output connected to
channel 1.
0 = Fill operation is disabled
1 = Fill operation is enabled.
O.Total[1].FillStart Decimal BOOL Begins filling operation when Fill Enable is enabled on
output connected to channel 1.
0 = Do not begin filling
1 = Begin filling
O.Total[1].FillHold Decimal BOOL Holds/pauses filling operation on output connected to
channel 1.
0 = Continue filling operation
1 = Hold/pause filling operation
O.Total[1].RollOverValue Decimal DINT Sets the user-defined rollover value on output
connected to channel 1.
Range of 0 - 2,147,483,647
O.Total[1].CombinedCorrectionFactor Float REAL Unitless factor that is multiplied by Gross Rate with
results shown as NetRate of channel 1.
This value must be set to 1.0 when not used or gross
rate will be 0.
Calculation Type must be set to 0 to use this factor.
O.Total[1].BaseTemperature Float REAL Temperature in °F of output connected to channel 1.
O.Total[1].FlowingTemperature Float REAL Temperature in °F of output connected to channel 1.
O.Total[1].AtmosphericPressure Float REAL Pressure in psia of output connected to channel 1.
O.Total[1].StaticGaugePressure Float REAL Pressure in psig of output connected to channel 1.
O.Total[1].BasePressure Float REAL Pressure in psig of output connected to channel 1.
O.Total[1].BaseCompressibility Float REAL Default = 1
O.Total[1].FlowingCompressibility Float REAL Default = 1
O.Total[1].FillTotalTarget Float REAL Target for Fill Complete, except when Fill Transition is
greater than this value.
O.Total[1].FillTransition Float REAL When fill cycle is started, trickle flow is initiated when
the Fill Total is equal to or greater than this value. Full
flow is initiated when the Fill Total is less than this
value.
Table 15 - Configurable Flowmeter Module Output Tags