155Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
Configure Output Behavior with RSLogix 5000 Version 16 and Earlier 155
Specify the Configurable On/Off Behavior
1. In the previously existing program, select the Controller Tag folder and
view the Monitor Tags tab.
2. Expand the CFM_B_C tag until you reach the
CFM_B_C.OutputWindow data tags.
3. In the Value column of the CFM_B_C.OutputWindow data tags, enter
the desired the On and Off frequency limits.
See Table 5 on page 58
for more information about determining your
On/Off frequency limits.
4. Edit existing tag references throughout the project so they link to the
appropriate, newly-added, user-defined tags.
For example, if the tag reference is Local:5:I.Status.FreqAverage, change
it to the corresponding user-defined tag, CFM_IN.Status.FreqAverage.
IMPORTANT
Test the configuration before implementing the changes
into your production process.