133Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
Software Configuration Tags 133
O.Total[0].RollOverValue Decimal DINT Sets the user-defined rollover value on output
connected to channel 0.
Range of 0 - 2,147,483,647
O.Total[0].CombinedCorrectionFactor Float REAL Unitless factor that is multiplied by Gross Rate with
results shown as NetRate of channel 0.
This value must be set to 1.0 when not used or gross
rate will be 0.
Calculation Type must be set to 0 to use this factor.
O.Total[0].BaseTemperature Float REAL Temperature in °F of output connected to channel 0
O.Total[0].FlowingTemperature Float REAL Temperature in °F of output connected to channel 0
O.Total[0].AtmosphericPressure Float REAL Pressure in psia of output connected to channel 0
O.Total[0].StaticGaugePressure Float REAL Pressure in psig of output connected to channel 0
O.Total[0].BasePressure Float REAL Pressure in psig of output connected to channel 0
O.Total[0].BaseCompressibility Float REAL Default = 1
O.Total[0].FlowingCompressibility Float REAL Default = 1
O.Total[0].FillTotalTarget Float REAL Target for Fill Complete, except when Fill Transition is
greater than this value.
O.Total[0].FillTransition Float REAL When fill cycle is started, trickle flow is initiated when
the Fill Total is equal to or greater than this value. Full
flow is initiated when the Fill Total is less than this
value.
O.Total[0].FillTransitionTimer Float REAL When timed trickle flow is selected, the status remains
ON for this time during this state.
The value must be changed prior to entering the trickle
flow state.
O.Total[1].AlarmEnables Binary SINT
O.Total[1].Overrange Decimal BOOL Enables the Overrange alarm on output connected to
channel 1. When the Frequency Period exceeds 100KHz,
this alarm is set.
0 = No Alarm
1 = Alarm Enabled
O.Total[1].Overflow Decimal BOOL Enables the Overflow alarm on output connected to
channel 1. When the Total Counts exceeds the Roll Over
value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
O.Total[1].Overspeed Decimal BOOL Enables the Overspeed alarm on output connected to
channel 1. When the Speed exceeds the Highest
Allowed Frequency value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
O.Total[1].Acceleration Decimal BOOL Enables the Acceleration alarm on output connected to
channel 1. When the absolute acceleration exceeds the
Acceleration Alarm value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
Table 15 - Configurable Flowmeter Module Output Tags
Name Style Data type Definition