File Operations
Chapter 6
6-11
Table 6.B
Communication
Settings
Available
on PanelView T
erminals
Baud Rate 300 600 1200 2400 4800 *9600 19200
Parity Type odd even *none
Data Bits 7 *8
Stop Bits *1 2
Handshake Type *Hardware Software
Auto Line Feed *Off On
Auto Form Feed *Off On
*default settings
5. Press Save & Exit, and you return to the Configuration menu.
Setting Upload/Download Communications on the PanelBuilder
Computer
For uploading and downloading, the communication settings on the
PanelBuilder computer must match those of the PanelView terminal. The
default settings of the PanelBuilder software (indicated by * in Table 6.C)
are the same as the default settings of the PanelView terminal (indicated
by * in Table 6.B).
You can change the communication settings for either of the COM ports if
you wish. Also, you can configure one of the COM ports for
upload/download, and the other for printing (see Step 6 of Printing Reports
described earlier in this chapter).
1. From PanelBuilder’s Main menu, choose Transfer.
2. In the Transfer menu, choose Download to PanelView Terminal
(RS-232).
3. Select a file and press Enter. The Select File window opens.
4. Choose Configure Port from the Select File menu. The available port
and communication settings are as follows:
Table 6.C
Upload/Download
Communication Settings A
vailable in PanelBuilder
Port COM1 COM2
Baud Rate 300 600 1200 2400 4800 *9600 19200
Parity Type odd even *none
Data Bits 7 *8
Stop Bits *1 2
*default settings