Troubleshooting
Appendix B
B-8
Problem What to doCause
While trying to download an application file,
a PROBLEM window appears stating: Error
code 208 was returned by the PassThrough
Utility."
The PassThrough Utility has been unable to
establish DH+ communications with the PLC5.
Make sure the Programming Terminal DH+
Address" and the PLC DH+ Address" are
properly assigned.
Make sure that you have selected the proper
DH+ Hardware Driver" for your system, and that
the DH+ Driver Card Location" code is correct.
Immediately after completing a PLC5
PassThrough Download, a Minor Fault
Status bit is set in the PLC5.
The rack assignment configuration of the
application file downloaded to the PanelView did
not exactly match the application file that was
overwritten.
Use the PLC5 6200 Series software to clear the
Minor Fault; then reconfigure the PLC5 to
recognize the new rack assignment.
Table B.G
PLC
Series/Revision Requirements for PassThrough File T
ransfer
Processor Series Revision
PLC5/11 All All
PLC5/15 B N or later
PLC5/20 All All
PLC5/25 A J or later
PLC5/30 A B or later
PLC5/40 A
B
E or later
B or later
PLC5/60 A
B
E or later
B or later
PLC5/250 All All