File Operations
Chapter 6
6-16
PanelBuilder version 3 and later software and PanelView version 3 and
later firmware support the uploading and downloading of application files
over the Allen-Bradley Data Highway +, using the PLC-5 Remote I/O
Pass-Through feature, with the PanelView terminal connected as a remote
I/O device to the PLC-5. This feature allows you to download application
files to PanelView terminals without changing cabling on the terminals,
and without having to go from terminal to terminal with a PC for direct
downloading.
Figure 6.14
Connecting
the Development Computer and PanelV
iew T
erminal through a Data
Highway + and PLC5
23633
PanelView
PLC-5
DH+
Remote
I/O
These PLC revisions support the Pass-Through feature:
Table 6.D
PLC
Series/Revision Requirements for PassThrough File T
ransfer
Processor Series Revision
PLC5/11 All All
PLC5/15 B N or later
PLC5/20 All All
PLC5/25 A J or later
PLC5/30 A B or later
PLC5/40 A
B
E or later
B or later
PLC5/60 A
B
E or later
B or later
PLC5/250 All All
Downloading and Uploading