PLC Programming Considerations
Appendix A
A-37
Create the Option Style Number Input Rung
When the operation is in Manual mode and the numeric keypad enable
object Enter key is pressed, Rung 2.8 transfers the new Option style
number value to the currently selected station’s option style address. It uses
the Cursor Indicator address as its pointer.
Figure A.22
The
Option Style Number Input Rung
23722
Rung 2:8
MANUAL
MODE
B40
] / [
1
CHANGE
STYLE NO.
ENTER KEY
N30:3
] [
MOV
MOVE
Source
Dest
6
N30:4
0
N35[N30:1]
100
Create the Manual On / Manual Off Input Rung
Rung 2:9 allows you to change the command value for the selected station
to Manual On or Manual Off while in Manual mode. This rung uses the
Cursor Indicator Address to place the command value in the proper
command file (N34, word address 1 through 57). It also updates the Status
File (N33) accordingly.