Troubleshooting
Appendix B
B-5
Table B.D
PanelView
Minor Fault Messages
Minor Fault Message Cause What to do
Retentive data initialization failed. There is no valid application file. Go offline and download the file again.
Audio hardware initialization failed. There is an audio hardware problem. Servicing by AllenBradley is required.
Terminal can't keep up with activity. Too much incoming data. The operator should stop all input until the
PanelView Terminal can process data.
Invalid Powerup Screen. Powerup screen does not exist or is faulty. Reassign the Powerup Screen or check the
configuration data in the PanelBuilder
application file.
User EPROM/EEPROM is not installed or is
corrupted.
Optional EPROM or EEPROM was not found or
is faulty.
If no user EPROM or EEPROM is installed,
ignore this message. You can disable the test
and the message in the Configuration Mode
Menu.
If a user EPROM or EEPROM is installed,
replace it.
Battery test failed. User RAM will be lost on
power down.
The battery for application file memory is dead. Upload the application file and save it on disk.
Servicing by AllenBradley is required.
Communication Self Test failed. The communication card is defective or not
installed.
Servicing by AllenBradley is required.
Invalid Screen. The PLC controller has selected a nonexistent
screen number.
Reprogram the PLC controller or the application
file.
Unable to write downloaded data to the
EEPROM.
The EEPROM or user memory configuration
jumpers are set incorrectly.
Check the EEPROM and user memory
configuration jumper settings.
Value Out Of Range. Address not sufficient for data transfer.
Current screen number transfer to PLC
controller is not sufficient.
Numeric entry or display address length is
insufficient for data.
Increase bit length of address so it's large
enough for screen transfer, including Alarm
History and Alarm Status screens.
Increase address length for data.
PLC currently controls screen change. PLC controller has control of screen change. Disable PLC Controlled Screen Change.
Clear PLC Controlled Screen Change register.
Reset to 0.
No screen changeHold Time in effect or no
PLC Handshake.
Operator is trying to change screens while a
button's hold time is still in effect or before an
activated Latched Push Button has received a
handshake.
Wait until hold time is finished or Latched
handshake is received before trying to change
screens.