144 Publication 2711-UM014G-EN-P - September 2008
Chapter 7 Installing the PV300 Terminal
6. Install the self-locking nuts hand tight.
7. Alternately tighten the self-locking nuts until the terminal is held
firmly against the panel
8. Tighten the nuts to a torque of 1.13 Nm (10 lb-in).
Do not over-tighten.
9. Remove the protective installation label covering the top vents
of the terminal.
ATTENTION
Mounting nuts must be tightened to a torque of 1.13 Nm
(10 lb-in) to provide a proper seal and to prevent
potential damage to the terminal. Allen-Bradley
assumes no responsibility for water or chemical damage
to the terminal or other equipment within the enclosure
because of improper installation. A properly installed
terminal has a small gap between the bezel and
enclosure.
ATTENTION
Failure to remove the protective installation label
covering the top vents could result in overheating and
damage to the terminal.
Self-locking nuts
(4 used, 6 provided)
Mounting Studs (2 left, 2 right)
Protective installation label