Publication 2711-UM014G-EN-P - September 2008 77
Configuring the Terminal Chapter 3
DH+ Communication
The DH+ screen lets you display or modify communication settings
for the DH+ version of the PanelView terminals.
Node
Opens the numeric entry scratchpad. Enter the node address (0…77
octal) of the terminal on the DH+ link and press the Enter ↵ key. (On
touch screen terminals, press the Enter key on the scratchpad). A
node change takes effect immediately.
Baud
Steps through the communication rates with each key press: 57.6K
(default), 115.2K, and 230.4K. The selected rate takes effect
immediately. The maximum cable length is restricted at higher
communication rates.
Comm Status Indicator
• solid fill - normal operating state
• blinking - no communication established
• no fill - hardware failure
Fault Status Indicator
• no fill - normal operating state
• blinking - hardware is functioning but an application is not
loaded or the current application is corrupted.
• solid fill - hardware failure
IMPORTANT
Settings downloaded with a DH+ application take priority over
terminal settings and take effect immediately after the
download.
DH+
Node:
Baud:
F1
F2
57.6 K
Comm
F16
EXIT
LED
Fault
LED
2
Comentarios a estos manuales