Rockwell-automation 2711 Standard PanelView Operator Terminal User Man Manual de usuario Pagina 240

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 292
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 239
240 Publication 2711-UM014G-EN-P - September 2008
Appendix A Specifications
Character Sizes (Pixel size = 0.35 x 0.35 mm)
PanelView 900
Monochrome and Color
(1)
Terminals
Terminal Memory
Total Application Flash Memory 240K bytes (application screens)
Environment
Operating Temperature 0…50 °C (32…122 ° F)
Storage Temperature -25…70 ° C (-13…158 °F)
Relative Humidity (non-condensing) 5…95% at 0…40 ° C (32…104 °F)
Heat Dissipation 17 W (577 BTU/HR)
Shock (operating/non-operating) 15 g/30 g
Vibration (operating) 2 g up to 2,000 Hz
Size in Pixels
width x height)
Characters/Row Maximum Rows Dimensions in mm
Width x Height
6 x 9 52 25 2.1 x 3.1
8 x 16 39 14 2.8 x 5.6
8 x 24 39 9 2.8 x 8.4
16 x 24 19 9 5.6 x 8.4
24 x 32 13 7 8.4 x 11.1
32x 40 9 5 11.1 x 13.9
(1)
The PanelView 900 specifications are for reference only. PanelView 900 Terminals are n longer available. Contact your Rockwell Automation distributor for more
information.
Electrical
AC Power - PV900M and PV900C
Supply Voltage Limits
Power Consumption
85…264V AC, 47…63 Hz
110 VA maximum
DC Power - PV900M
Supply Voltage Limits
Power Consumption
DC Power - PV900C
Supply Voltage Limits
Power Consumption
18…30 V DC (24V DC nominal)
58 W max (2.5 A @ 24V DC)
18…32 V DC (24V DC nominal)
50 W max (2.1 A @ 24V DC)