59Publication 2711-UM014G-EN-P - September 2008 59
Chapter
2
Applying Power and Resetting Terminal
Chapter Objectives
This chapter provides information on:
wiring and safety guidelines.
connecting AC or DC power.
resetting the terminal.
power-up sequence.
Wiring and Safety
Guidelines
Use publication NFPA 70E, Electrical Safety Requirements for
Employee Workplaces when wiring the PanelView terminals. In
addition to the NFPA general guidelines:
connect the terminal to its own branch circuit.
the input power should be protected by a fuse or circuit breaker
rated at no more than 15 Amps.
route incoming power to the PanelView terminal by a separate
path from the communication cable.
where power and communication lines must cross, they should
cross at right angles. Communication lines can be installed in the
same conduit as low level DC I/O lines (less than 10V).
IMPORTANT
Do not run signal wiring and power wiring in the same
conduit.