Rockwell-automation 2711 Standard PanelView Operator Terminal User Man Manual de usuario Pagina 194

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 292
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 193
194 Publication 2711-UM014G-EN-P - September 2008
Chapter 12 Terminal Connections
The DH-485 connectors are not electrically isolated. If electrical
isolation is required, use Link Couplers (Cat. No. 1747-AIC) as shown
on next page.
Connecting to a DH-485 Network
This section shows how to connect a DH-485 terminal to multiple SLC
controllers on a DH-485 network through the AIC Link Coupler.
ATTENTION
Electrical isolation using Link Couplers (Cat. No. 1747-AIC) is
required where the distance between the PanelView terminal
and the SLC is greater than 6.1 m (20 ft).
TIP
For PanelView 300 Micro terminals, refer to page 218
.
IMPORTANT
The DH-485 network cable requires proper shielding, grounding
and termination. Refer to Data Highway / Data Highway Plus /
Data Highway-485 Cable Installation Manual, publication
1770-6.2.2).
Belden 9842
Power Source
or 1747-NP1
SLC
SLC 5/01
PanelView 1000
Cable
Catalog No. 1747-C10
Catalog No. 1747-C11
Catalog No. 1747-C20
Link Coupler Catalog
No. 1747-AIC
Vista de pagina 193
1 2 ... 189 190 191 192 193 194 195 196 197 198 199 ... 291 292

Comentarios a estos manuales

Sin comentarios