Rockwell-automation 2711P PanelView Plus Terminal User Manual Manual de usuario Pagina 103

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 246
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 102
Publication 2711P-UM001J-EN-P - November 2009 103
Configuration Mode Chapter 4
2. Press the Memory Allocation button to view or adjust the:
amount of allocated storage or program memory.
amount of storage or program memory in use.
3. Press the Up or Down button to increase or decrease the
allocation of storage or program memory.
Each button press changes the allocation by a value of four. If
you change the allocation for one type of memory, the other is
updated accordingly.
4. Press OK to return to previous screen.
5. Press OK to return to terminal settings.
IMPORTANT
These settings are not retained after a power cycle. The
settings return to the defaults.
Vista de pagina 102
1 2 ... 98 99 100 101 102 103 104 105 106 107 108 ... 245 246

Comentarios a estos manuales

Sin comentarios