Rockwell-automation 2711P PanelView Plus Terminal User Manual Manual de usuario Pagina 181

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 246
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 180
Publication 2711P-UM001J-EN-P - November 2009 181
Terminal Connections Chapter 7
Remote I/O Connections
Use the Belden 9463 twin axial or equivalent cable (cat. no. 1770-CD),
to connect a terminal to a Remote I/O scanner. The maximum cable
length (link distance) is determined by the baud rate.
2800 m (10,000 ft) for 57.6 Kbps
1400 m (5,000 ft) for 115.2 Kbps
700 m (2,500 ft) for 230.4 Kbps
See Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
. The user manual for the I/O scanner module
also provides cabling information.
PanelView Plus 700 to 1500 Terminals
PanelView Plus 400 and 600 Terminals
82 Ω terminating resistor for 230.4 Kbps
150 Ω terminating resistor for 57.6 Kbps
and 115.2 Kbps
82 Ω terminating resistor for 230.4 Kbps
150 Ω terminating resistor for 57.6 Kbps
and 115.2 Kbps
Belden
To Controller
To Controller
Terminating Resistor
Terminating Resistor
Clear 1
Shield SH 2
Blue 3
Clear 3
Shield SH 2
Blue 1
Belden
Remote I/0 Port on Communication Module
Remote I/0 Port on Communication Module
Vista de pagina 180
1 2 ... 176 177 178 179 180 181 182 183 184 185 186 ... 245 246

Comentarios a estos manuales

Sin comentarios