31Publication 2711P-UM001J-EN-P - November 2009 31
Chapter
2
Installation
Chapter Objectives
This chapter provides pre-installation information and procedures on
how to install the terminals.
Hazardous locations
Environment and enclosure
Outdoor installation for 1250 high-bright display module
Required tools
Clearances
Panel cutout dimensions
Mount the 400 or 600 terminal in a panel
Mount the 700 to 1500 terminals in a panel
Product dimensions
Hazardous Locations
When marked, this equipment is suitable for use in these locations:
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, Group IIC
Class II, Division 2, Groups F, G
Class III
ordinary, nonhazardous locations
The following statement applies to use in hazardous locations.
WARNING
Explosion Hazard
Do not disconnect equipment unless power has been removed and
area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has
been removed and the area is known to be nonhazardous.
Substitution of components may impair suitability for
Class 1, Division 2.
Peripheral equipment must be suitable for the location it is used in.
The battery or realtime clock module in this product must only be
changed in an area known to be nonhazardous.
All wiring must be in accordance with Class I, Division 2, Class II,
Division 2, or Class III, Division 2 wiring methods of Articles 501, 502
or 503, as appropriate, of the National Electrical Code and/or in
accordance with Section 18-1J2 of the Canadian Electrical Code, and
in accordance with the authority having jurisdiction.