158 Publication 2711P-UM001J-EN-P - November 2009
Chapter 6 Install and Replace Components
4. Attach the touch screen connector.
5. Replace the sealing gasket.
6. Attach the screws that secure the display module to the bezel
and tighten to a torque of 1.35…1.58 Nm (12…14 lb•in).
7. On touch screen terminals, reattach the small metal plate to the
back of the display module using two screws and torque to
0.58 Nm (5…7 lb•in).
Replace the Backlight
This section shows how to replace the backlight for the 700, 1000,
1250, and 1500 terminals. The 1250 high-bright terminals do not have
a replaceable backlight.
Follow these steps to replace the backlight.
1. Disconnect power from the terminal.
2. Remove the display module bezel.
3. Remove the four screws that secure the display bracket for the
700 series C display.
Backlights for PanelView Plus 700 to 1500 Displays
Use Cat. No. For Display Series # of Backlights
2711P-RL7C 700 A and B 1
2711P-RL7C2 C 1
2711P-RL10C 1000 A 1
2711P-RL10C2 B and C 1
2711P-RL12C 1250 A and B 2
2711P-RL12C2 C 1
2711P-RL15C 1500 B 2
IMPORTANT
Disposal: The backlights for these products contain mercury.
Dispose of per applicable laws.
IMPORTANT
The 700 series C display is not secured by screws and is only
retained by a bracket. Use care not to drop the display once the
bezel is removed.