Bulletin 284 Programmable Parameters for Sensorless Vector Controllers 4-33
Table 4.4 Parameter 158 and 161 Options
Relay Out Level
Sets the trip point for the digital output relay if the value of Parameter 155 (Relay
Out Sel) is 6, 7, 8, 10, 16, 17, 18, or 20.
Parameter Number 156
Related Parameters 155, 158, 161
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units 0.1
Minimum Value 0.0
Maximum Value 9999
Default Value 0.0
Parameters 155 Setting Parameter 156 Min./Max.
6 0/400 Hz
7 0/180%
8 0/815V
10 0/100%
16 0.1/9999 sec
17 1/9999 counts
18 1/180°
20 0/1
158 (Opto Out1 Sel)
161 (Opto Out2 Sel)
Determines the operation of the programmable opto outputs.
Parameter Number 158, 161
Related Parameters
133, 156, 192, 240…247,
250…257
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units
See Table 4.4 for details
Minimum Value
Maximum Value
Default Value
Options Description
0
Ready/Fault
(Default)
Opto outputs are active when power is applied. This indicates the drive is ready for operation. Opto outputs are
inactive when power is removed or a fault occurs.
1
At Frequency
(Parameter 161
Default)
Drive reached commanded frequency.
2
MotorRunning
(Parameter
158Default)
Motor is receiving power from drive.
3 Reverse Drive is commanded to run in reverse direction.
4 Motor Overld Motor overload condition exists.
5 Ramp Reg
Ramp regulator is modifying the programmed accel/decal times to avoid overcurrent or overvoltage fault from
occurring.
6 Above Freq
Drive exceeds the frequency (Hz) value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto Output 2
Level) Use Parameter 159 or 162 to set threshold.
7 Above Cur
Drive exceeds the current (% Amps) value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto Output
2 Level). Use Parameter 159 or 162 to set threshold. Important: Value for Parameter 159 or 162 must entered in
percent of the drive rated output current.
8 Above DCVolt
Drive exceeds the DC bus voltage value set in Parameter 159 (Opto Out 1 Level). Use Parameter 159 or 162 to set
threshold.
9 Retries Exst Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.
10 Above Anlg V Option not valid for Bulletin 284 ArmorStart.