Bulletin 280/281 CIP Information B-9
Table B.26 Instance 163 is the standard input (produced) assembly with
Network Outputs and ZIP CCV
Table B.27 Instance 190 is the 1999-ZCIO Native Format Produced Assembly
Instance 163 — Standard Produced Starter with Network Outputs
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Ready
Running
Rev
Running
Fwd
Warning Tripped
1— 140M On
HOA
Stat.
User In 4 User In 3 User In 2 User In 1
2 Net Out 8 Net Out 7 Net Out 6 Net Out 5 Net Out 4 Net Out 3 Net Out 2 Net Out 1
3
Logic
Enabled
Net Out
15
Net Out
14
Net Out
13
Net Out
12
Net Out
11
Net Out
10
Net Out 9
4ZIP CCV (Low)
5 ZIP CCV (High)
Instance 190 — 1799-ZCIO Native Format Produced Assembly
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
Running
Rev
Running
Fwd
Warning Tripped Input 3 Input 2 Input 1 Input 0
1 Reserved
Logic
Enabled
Reserved 140M On HOA
2 Reserved
User Out
B
User Out
A
Run Rev Run Fwd
3Reserved
4 Net Out 8 Net Out 7 Net Out 6 Net Out 5 Net Out 4 Net Out 3 Net Out 2 Net Out 1
5ZIP CCV (Low)
6 ZIP CCV (High)