Bulletin 280/281 Programmable Parameters 3-9
Bulletin 280 products.
Bulletin 281 products.
Produced I/O Size
This parameter reflects the
produced I/O data size in bytes.
Parameter Number 18
Access Rule GET
Data Type USINT
Group DeviceNet
Units
Minimum Value 0
Maximum Value 8
Default Value 2
Starter COS Mask
This parameter allows the
installer to define the change-of-
state conditions that will result in
a change-of-state message
being produced
Parameter Number 19
Access Rule GET/SET
Data Type WORD
Group DeviceNet
Units
Minimum Value 0
Maximum Value 16383
Default Value
16149
16157
Bit
Function
13 12 11 10 9 8 7 6 5 4 3 2 1 0
————————————— X Tripped
———————————— X Warning
—————————— X —— Running Fwd
—————————— X ——— Running Rev
————————— X ———— Ready
———————— X ————— Reserved
——————— X —————— Reserved
—————— X ——————— Reserved
————— X ———————— Input 0
———— X ————————— Input 1
——— X —————————— Input 2
—— X ——————————— Input 3
— X ———————————— HOA Status
X ————————————— 140M On