13.0 ONLINE MENU: INFO/LOG
Entering
I" for Info/Log from the Online menu allows you to display
information about the system software on any AutoMax Processor,
PC3000 Processor, or UDC module in the rack or to view the status
and error log, if any, for a selected task.
13.1 Info/Log Processor and UDC Information
Display
If you select Info/Log without having selected a task by using the
Enter key or <CR>, AutoMax will assume you want to display
information about an AutoMax Processor and the Common Memory
module (M/N 57C413B or 57C423), a PC3000 Processor
, or a UDC
module. You will be prompted for the slot number of the module of
interest.
AutoMax Processor or PC3000 Processor
Figure
13.1 shows a sample display for an AutoMax Processor in slot
1 with no Common Memory module. Figure 13.2 shows a sample
internal PC3000 Processor.
ON LINE Direct via Serial C: \LIB\SYS\RACK
EscăExit
Info/Log
Control Processor Information for Slot 1
CPU Error Code: N/A Network Error Code: N/A
AB Remote I/O Error Code: N/A Network Drop: N/A
Software ID: 422526Ć001C STD
Clock T
ick (micro sec):
5500
CPU Utilization: 34%
Memory Memory Largest
Used
F
ree Free Block Battery
PROCESSOR 2924 151280 151280 Replace
COMMON N/A
N/A
N/A
N/A
Figure 13.1 Ć Info/Log Processor Information Display