AutoMax ControlNet Module Page 39
Publication number DSMBCN-UM001B-EN-P February 2003
If bit 3 is set, one or more originator instances does not have a schedule.
Run RSNetWorx and schedule the network by enabling edits and doing a
save.
Scanner State
Register 15754 shows the current scanner state.
Value Scanner State
0 Idle
1 Active, in program mode
2 Active, in run mode
Figure 6 Scanner State Table
This register is read-only. The state is Idle only when you are
downloading a configuration.
Adapter State
Register 15755 shows the current state of scheduled produced data
connections.
Value State
0 Idle
1 Enabled
Figure 7 – Adapter (Scheduled Produced Data) State Table
This register is read-only.
Summary of Registers for Monitoring Operation
Refer to the preceding sections for detailed information on each of these
registers.
AutoMax
Registers
Name Description
15362 -
15615
Connection
status
Status of each connection
15745 Status Overall status
15748 NumInstances Number of instances currently
configured
15751 NumOrigInsts Number of originator instances
15754 ScanState Current scanner state