Page 66 AutoMax ControlNet Module
Publication number DSMBCN-UM001B-EN-P February 2003
Name Location Description
ReplySentOk 9385 High Level Replies Sent OK
ReplyRecdOk 9386 High Level Replies Received OK
DuplMsgsRecd 9387 Duplicate Messages Received (and ignored)
AckTout 9388 UCMM Acknowledge Timeouts
TxFail 9389 High Level Transmit Failures, the MBCN tried
3 times to send a message, there was no
acknowledge, no reply
UndelivReply 9390 High Level Reply could not be delivered
ConnTimeout 9391 Connection TimeOuts
MsgsIgnored 9392 Messages Ignored, caused by other nodes
sending diagnostic messages on the network
MsgsIgnType 9393 Type of Message Ignored
FreeUnsBufs 9394 Free Unscheduled Buffers
FreeHeapBlks 9395 Free Internal Heap Blocks
EventOveruns 9396 Event Overruns
ConnRetries 9397 Connected Message retries
ConnRefSts 9398-9399 The status of the last refused connection. The
upper byte of 9399 contains the general status.
The lower byte of 9399 contains the length of
the extended status, either 0 (no extended
status) or 2. Register 9398 contains the
extended status, if present.
NapRxBad 9400 NAP frames received with a bad CRC
NapRxAbt 9401 NAP receive abort frames
Figure 26 Module-Specific Diagnostic Counters
The Error Log
Registers 9336-9339 contain the error log. This is a log of the source
addresss for the last eight messages with CRC errors or transmit abort
errors. Each register contains two error log entries, one byte each.
NOTE: Since these errors occur when the MBCN receives bad packets,
the contents of the log may not be valid, but it may be useful in
identifying problem nodes.
The error log is a ring buffer.