Rockwell Automation Publication IASIMP-QS028A-EN-P - July 2012 33
Create DeviceNet Network Software Files Chapter 2
Associate the DeviceNet Configuration File with an RSLogix 5000 Project
You must associate the DeviceNet network configuration file with your RSLogix 5000 project.
1. Verify the controllers mode switch
is in the PROG position.
2. Open a new RSLogix 5000
project.
3. Add the appropriate DeviceNet
scanner module to the controller’s
I/O configuration.
This example uses a 1769-SDN
scanner module in a
CompactLogix 5370 L3 controller
project.
4. Configure the scanner module’s
parameters on the General and
Connection tabs as desired.
TIP
If you already created an RSLogix 5000 project for your Logix5000 controller, as described in Logix5000 controller quick
starts, go to step 5 on page 34.
RUN
REM
PROG