Chapter 3 Use a PowerFlex 40 Drive in an RSLogix 5000 Project
Test the PowerFlex 40 Tags
1. Move the controller’s mode switch
to the RUN position.
2. In the configuration tree, double-
click Controller Tags.
3. Change the tag
O.CommandRegister.Run
tag to 1.
The 1769-SDN scanner module
transitions to Run mode.
4. Expand the PowerFlex 40
output tag.
In this case the tag is named Local_SDN_scanner_module_N02_POL_O.
5. Change the O.Reference tag to a value of 10.
The value 10 equals 1.0 Hz. This is the speed to which your drive accelerates.
PowerFlex 40 tags are identified in the description column.