Rockwell Automation Publication IASIMP-QS028A-EN-P - July 2012 49
Use a PowerFlex 40 Drive in an RSLogix 5000 Project Chapter 3
6. Change the O.Start tag to a value
of 1.
The display on the drive registers
the speed increase in Hertz until
the value entered at the reference tag is reached.
7. Change the O.Start tag back to 0.
8. Change the O.Stop tag to 1.
The display on the drive shows a
speed decrease until the drive
reaches 0.00 Hz.
9. Change the Stop tag back to 0.
10. Select Go Offline.
By starting and stopping the drive, you
verified the following:
• The controller is correctly communicating with the drive.
• The drive can receive simple commands.