C-20
EtherNet/IP Communications Module
5 Set User Definable
Tex t
STRING[16] Text identifying the device with a
user-supplied name.
6 Get Status Text STRING[12] Text describing the status of the
device.
7 Get Configuration
Code
BYTE Identification of variations.
8 Get Configuration
Tex t
STRING[16] Text identifying a variation of a
family device.
9 Get Brand Code WORD 0x0002 = Reliance
11 Get NVS Checksum WORD Checksum of the non-volatile
storage in a device.
12 Get Class Revision WORD 2 = MDI
13 Get Character Set
Code
BYTE 0 = SCANport OIM
1 = ISO 8859-1 (Latin 1)
2 = ISO 8859-2 (Latin 2)
3 = ISO 8859-3 (Latin 3)
4 = ISO 8859-4 (Latin 4)
5 = ISO 8859-5 (Cyrillic)
6 = ISO 8859-6 (Arabic)
7 = ISO 8859-7 (Greek)
8 = ISO 8859-8 (Hebrew)
9 = ISO 8859-9 (Turkish)
10 = ISO 8859-10 (Nordic)
255 = ISO 10646 (Unicode)
15 Get Languages
Supported
STRUCT of
BYTE
BYTE[n]
Number of Languages
Language Codes (See Class
Attribute 2)
16 Get Date of
Manufacture
STRUCT of
WORD
BYTE
BYTE
Year
Month
Day
17 Get Product Revision STRUCT of
BYTE
BYTE
Major Firmware Release
Minor Firmware Release
18 Get Serial Number DWORD Value between 0x00 and
0xFFFFFFFF
Attribute
ID
Access
Rule Name Data Type Description
Vista de pagina 147